(To be performed ONLY by qualified service providers)
Save this manual for future reference
Manual 47132A
The Bradford White
R
U150L*FRN
U1504S*FRN
U430T*FRN
U440T*FRN
U4403S*FRN
U4503*FRN
U1XR403S*FRN
(*) Denotes Warranty Years.
U130T*FRN
U130S*FRN
U140T*FRN
U1403T*FRN
U1403S*FRN
U1404T*FRN
U1503*FRN
R
Page view 0
1 2 3 4 5 6 ... 27 28

Summary of Contents

Page 1 - The Bradford White

(To be performed ONLY by qualified service providers)Save this manual for future referenceManual 47132A The Bradford WhiteRU150L*FRNU1504S*FRNU430T*F

Page 3 - INTRODUCTION

THERMOPILE REPLACEMENTStep 1. Turn off gas supply to water heater. Rotate gas control knob to the “OFF” position.Step 2. Remove outer jacket door.Step

Page 4

PILOT/ELECTRODE ASSEMBLY INSPECTION,CLEANING AND REPLACEMENTStep 1. Turn off gas supply to water heater. Rotate gascontrol knob to the “OFF” position.

Page 5 - Indicator

IGNITER, ELECTRODE TESTING AND REPLACEMENTWith the pilot not in operation (no pilot flame) you can check the igniter and electrode circuit by viewing

Page 6 - Gas Control Troubleshooting

Thermal Well TestingThermal well testingPosition gas control knob to the “OFF” position and disconnect thermal well harness from gas control.NYUsing a

Page 7

°F012345678 940 26109 25400 24712 24045 23399 22771 22163 21573 21000 2044550 19906 19383 18876 18383 17905 17440 16990 16553 16128 1571560 15314 1492

Page 8 - Procedure

Gas Control & Thermal Well Removal From Water HeaterStep 1. Turn the gas control knob to the “OFF” position. Step 2. Drain heater to a point below

Page 9 - Pilot Tube and Igniter Wire

Gas Control Assembly to Thermal WellStep 6. Reconnect wire harnesses and igniter wire to gas control per the illustration to the left.Step 7. Reconnec

Page 10

Step 1. Turn the gas control knob to the “OFF” positionStep 2. Disconnect the chamber sensor wire harness from the gas valve.Step 3. Remove the chamb

Page 11 - Thermopile Position

At periodic intervals (not more then 6 months) a visual inspection should be made of the main burner for proper operation and to insure no debris is a

Page 12

The Bradford WhiteUltra Low NOx Gas Water HeatersPage Service Procedure Introduction 3 - - -Gas Control Troubleshooting Chart 5 - - -Tools Requi

Page 13 - Igniter Lead

Step 5. Disconnect (unscrew) manifold mount from feed line. Use a stiffbrush, compressed air and/or shop vacuum to remove any debris build up from the

Page 14 - Thermal Well Testing

Step 1. Remove outer jacket door.Step 2. Disconnect white wire leads from resettable thermal switch.Step 3. Using a multimeter capable of measuring co

Page 15

SERVICE PROCEDURE ED-VIIResettable Thermal SwitchTesting and ReplacementRESETTABLE THERMAL SWITCH REPLACEMENTStep 1. Rotate gas control knob to the “O

Page 16 - Thermal

SERVICE PROCEDURE ED-VIIIScreenLok Flame Arrestor CleaningStep 1. Rotate gas control knob to the “OFF” position.Step 2. Remove outer jacket door.Ste

Page 17

SERVICE PROCEDURE ED-IXDip Tube and AnodeInspection and ReplacementPage 24Step 1. Rotate gas control knob to the “OFF” position.Step 2. Turn off cold

Page 18

Step 1. Turn off water supply to water heater. Rotate gas control knob to the “OFF” position.Step 2. Turn off cold water supply to heater. Connect hos

Page 19 - BURNER CLEANING

1 Flue Baffle2 Hot Water Outlet/Anode3 Cold Water Inlet Tube4 T&P Relief Valve5 Thermal Well6 Brass Drain Valve7 Gas V

Page 21

[email protected]@bradfordwhite.comwww.bradfordwhite.com

Page 22 - Manifold Mount

The Bradford White ECO-DEFENDER Safety SystemThe Bradford White ECO-DEFENDER Safety System was designed to resist the ignition of flammable vapors tha

Page 23

It is intended for this manual to be used by qualified service personal for the primary purpose of troubleshooting and repair of the Bradford White EC

Page 24

Page 5LED Status Control Status Probable Cause Service ProcedureNone (LED not onor flashing)Gas valve is operating normally. Pilot flamemay not be pre

Page 25

Page 6LED Status Control Status Probable Cause Service ProcedureFive flashesand three secondpause.Thermostat well fault. 1. Damage to thethermowell wi

Page 26

Inner Door Removal ProcedureStep 1. Rotate the gas control knob to the “OFF” position.Step 2. Remove outer jacket burner access doorStep 3. Inner Do

Page 27

Installation of Inner Door With Gasket.WARNINGStripped fastener connections may allow for seal breach of inner door. A seal breach may result in a fir

Page 28

Step 10. Firmly place right side inner door flange against the burner door flange and secure with two ¼” drivescrews from step 3e. DO NOT OVER TIGHTEN